Fail safe stand-alone remote isolation system with continuous self-diagnostics
Time to isolate and lock out is as short as three minutes
Automated process completes isolations remotely without requiring the presence of personnel in substations or switchrooms, avoiding the risk of arc flash
Multiple independent verified points of isolation
Networks to existing plant DCS or SCADA system
Maintains integrity on power or communications outage
After installation, a time functionality proof test (TFPT) is required
Can perform up to the requirements for SIL3 and CAT4
Standard Compliance
AS 1755-2000 Conveyors - Safety Requirements
AS/IEC 62061-2005 Safety Machinery - Functional Safety of safety-related electrical, electronic and programmable electronic systems
AS/IEC 61508 Functional Safety - Safety Related Systems
ISO 13849 (EN 954) Safety of Machinery - Safety related parts of control systems
AS/IEC 61511 Functional Safety Instrumented Systems for Process Industry
Components Certification
Voltage monitors - TÜV certified SIL3/CAT4 Safety Voltage Monitor
CPU and I/Os - TÜV certified SIL3/CAT4 Safety PES hardware
Field Bus - TÜV certified SIL3/CAT4 Safety Protocol
Isolation Method
Additional safety contactors
Safety interlocks
Automated racking system
Remote isolation is available for LV up to 1,000VAC and HV 3.3 to 11kV
Voltage sensing and monitoring systems
Dual type - two voltage sensing channels with unit self-diagnostics
Architecture
One master controller
Multiple field stations
Field Isolation Stations
Interface for field operators provides all required functionality, indication with plain English messaging
Data transferred to site SCADA
Request to isolate and return to service
Alarm and statuses with time stamp
System status and self-diagnostic information